Introduction
Given the tube geometry
and coil dimensions ,the "COILS" program predicts the thermal performance
of various types of convective heat transfer surfaces with bare or finned
tubes in inline or staggered arrangement and in parallel or counter flow
configuration. By convective surfaces is meant is that external radiation
from a furnace or flame is not considered,though non-luminous heat transfer
coefficient is evaluated. Hence the program is suitable for predicting
the performance of induvidual coils such as:
1.water tube
boiler evaporator /HRSG evaporator
2.superheater
3.economizer
4.tubular air
heater(single, multiple pass)
5.steam-air heater
/air-cooled condenser
6.coil heating
industrial heat transfer fluids such as therminol/glycol
Note:This
is NOT a heat exchanger program. The fluid outside the tubes should be
either air or flue gas and not a liquid. Fluid inside can be steam, air
or flue gas, water, steam-water mixture or heat transfer fluid whose thermal,
transport properties are known.
The program may
be used to arrive at the geometry for a given duty or may be used to predict
the performance of an existing coil. By playing with variables such as
tube size,spacing,fin geometry,lengths,one can arrive at the optimum size
for a new application which matches the duty and gas/fluid pressure drops
desired.This is called the design mode. In the performance mode,one checks
the thermal performance for a given coil,whose geometry and dimensions
are known. For example the plant engineer may use it to see how the superheater
in the HRSG behaves under different conditions of steam flow, steam pressure,
gas flow or gas analysis. One can study if the economizer will “steam”
under new or different operating modes or compare the actual performance
with predicted and see if there is a possibility of fouling.Hence this
program may be used for a variety of purposes.
The cooling or heating
gas/air flows outside the bare or finned tubes while the fluid, such as
steam/water/liquid/gas/air flows inside the tubes. All the tubes of the
coil should have the same tube/fin configuration. If there are different
configurations within the coil such as two different fin geometries or
tube sizes, then the program may be run as many times as required, taking
the results from each run and inputting them as data for the next run.
The "COILS"
program computes several useful data for the coil as can be seen from the
DEMO. In addition to the duty and exit fluid temperatures for a wide variety
of bare/finned tube configurations, one can evaluate gas side pressure
drop, tube wall and fin tip temperatures at inlet and exit of the coil,fluid
velocities and heat transfer coefficients. With an economizer or superheater,for
example, the tube wall temperature at both inlet and exit of the coil are
computed so that concerns about acid dew point corrosion/material selection
may be addressed. Steaming if present in an economizer is also computed.
A wide variety of coils used in waste heat boilers, heat recovery equipment
and boiler plants can be evaluated with this program.
The program runs
on both British and Metric units. It runs on any Windows platform such
as Windows 95,98, NT or later versions with as little as 16 MB RAM memory
and on any processor. Hard disk space required is less than a MB.The DEMO
has two examples in it. In order to run the DEMO,do the following:
1.Create a directory
called VG
2.Download and save
the file "coilpgmd.exe" to the VG directory.(click below to download file)
3.on clicking this
file,all the files will expand.
4.run using the
command,"c:\vg\coild"
5.There are two
examples in the DEMO-Examples a and b. One for a superheater and one for
an economizer.Dont change any data and run these examples.
Example a
Data:A HRSG
superheater operates under the following conditions.
Flue gas flow=280000
lb/h
gas inlet temperature=950
F(analysis:% volume Co2=3,H2o=7,N2=75,O2=15)
gas inlet pressure=14.5
psia
fouling factors
on gas/steam side=0.001 ft2hF/Btu
heat loss=2 %
steam flow=100,000
lb/h
Inlet pressure=500
psia
inlet temperature=saturation
Coil data: 2 x1.738
in tube,22 tubes/row,6 deep,10 ft long; fins:3 x0.625x0.05 solid. 4 in
square inline arrangement, counter flow. Use 22 streams, correction factor=1.Fin
conductivity is typically 20-25 Btu/fthF.
Solution:Enter
the data as shown in the three forms .Select 1 for type in fluid data sheet.
Click Run and results appear as shown. {bml exama.bmp} It is seen that:
Duty=9.94 MM Btu/h
steam temperature
in=467 F,out=610 F
gas temperature
out=819 F
steam pr drop=8.3
psi(coil only)
gas pr drop=0.83
in wc(tubes only)
surface area=2894
ft2
overall heat transfer
coefficient=9.92 Btu/ft2hF
Exit tube wall temperature=703
F,fin tip temperature=766 F
Note that these
results have no margins. One may use a duty of say 9.8 MM Btu/h,steam
pressure drop=10 psi, gas pressure drop=1.25 in wc etc, depending on guarantees,
piping involved and additional gas/steam pressure drop etc.
By clicking the
menu item Report,one can get a summary of results,which is also saved with
extension .vgp.
Example b
This is an economizer;
Metric units are used.
Data:!00,000
kg/h of flue gas at 300 C enters a coil.Tubes are 51x45 mm,30 wide,12 deep,4
m long with bare tubes. Tube spacing is 76 mm inline.70,000 kg/h of Feed
water
at 23 kg/cm2a and at 111 C enters the unit. Fouling factors are 0.0002
m2hC/Kcal. Predict the performance.
Solution
Enter the data as
shown. Select 2 for fluid type.Enter the flow,temperature,pressure and
fouling factor.Click Run .It is seen that the exit gas temperature=220
C,water exit temperature=141 C,duty=2.11 MM Kcal/h. Gas pressure drop=26
mm wc and water side pressure drop=.77 kg/cm2.Add margins to the results
as required.
The program also
estimates the % weight of steam formed in case the economizer steams.This
situation is likely in gas turbine economizers at low loads.The program
also prints out the results in the format shown below,which is useful for
reporting.{bml report.bmp}
The file is saved
in a text format with the extension “vgp” to the project name. For example
“examplea” project would be saved as examplea.vgp. One can then import
in into any document or report.
PRICE : $
495 (email for purchasing information)
Download the
FREE (coilpgmd.exe file)DEMO program
Back to Ganapathy's
Home Page